Effect of saturation temperature and vapor quality on the boiling heat transfer and critical heat flux in a microchannel
Özet
In this paper, heat transfer coefficients and critical heat fluxes of the R134a fluid in two-phase flow was studied in a 27-channel, 421 μm hydraulic diameter and 40 mm long microchannel experimental set-up. Data were collected at constant mass flux of 1000 kg m−2 s−1, saturation inlet temperature range of 20–28 °C and at inlet vapor quality range of 0.01–0.20. The heat flux was initiated at 250 kW m−2 and gradually increased until reaching the critical heat flux (CHF). The effect of inlet vapor quality, saturation inlet temperature and heat flux on heat transfer coefficient and critical heat flux were investigated in detail and presented graphically. It can be observed that the CHF decreases with the increasing of saturation inlet temperature and inlet vapor quality. However, the heat transfer coefficient at the CHF point increased with the increasing of saturation temperature and the heat transfer coefficient at the CHF point was decreased with the increasing of vapor quality. The test results from the correlations, suggested in well-known articles, were compared with the experimental data, where the Kosaz et al. proposed correlation was showing well fit with the experimental data having absolute error of 9.86%. In this investigation, the new correlations for the heat transfer coefficient for the heat transfer coefficient and the critical heat flux have been proposed by taking into account the effect of the vapor quality. © 2020 Elsevier Ltd
Anahtar Kelimeler
Tam Kayıt
| Alan | Değer | Dil |
|---|---|---|
| dc.contributor.author | Dalkılıç, Ahmet Selim | |
| dc.contributor.author | Celen, Ali | |
| dc.contributor.author | Erdoğan, Murat | |
| dc.contributor.author | Sakamatapan, Kittipong | |
| dc.contributor.author | Newaz, Kazi Salim | |
| dc.contributor.author | Wongwises, Somchai | |
| dc.date.accessioned | 2026-10-18T20:28:10.319959449Z | |
| dc.date.available | 2026-10-18T20:28:10.319959449Z | |
| dc.date.issued | 2020 | |
| dc.description.abstract | In this paper, heat transfer coefficients and critical heat fluxes of the R134a fluid in two-phase flow was studied in a 27-channel, 421 μm hydraulic diameter and 40 mm long microchannel experimental set-up. Data were collected at constant mass flux of 1000 kg m−2 s−1, saturation inlet temperature range of 20–28 °C and at inlet vapor quality range of 0.01–0.20. The heat flux was initiated at 250 kW m−2 and gradually increased until reaching the critical heat flux (CHF). The effect of inlet vapor quality, saturation inlet temperature and heat flux on heat transfer coefficient and critical heat flux were investigated in detail and presented graphically. It can be observed that the CHF decreases with the increasing of saturation inlet temperature and inlet vapor quality. However, the heat transfer coefficient at the CHF point increased with the increasing of saturation temperature and the heat transfer coefficient at the CHF point was decreased with the increasing of vapor quality. The test results from the correlations, suggested in well-known articles, were compared with the experimental data, where the Kosaz et al. proposed correlation was showing well fit with the experimental data having absolute error of 9.86%. In this investigation, the new correlations for the heat transfer coefficient for the heat transfer coefficient and the critical heat flux have been proposed by taking into account the effect of the vapor quality. © 2020 Elsevier Ltd | |
| dc.description.sponsorship | All authors would like to express thanks to King Mongkut's University of Technology Thonburi for the funding during this investigation in Thailand. The fourth author acknowledges the financial support provided by the “Research Chair Grant” National Science and Technology Development Agency (NSTDA), the Thailand Research Fund (TRF) and King Mongkut's University of Technology Thonburi through the “KMUTT 55th Anniversary Commemorative Fund”. The first author wish to show gratitude to KMUTT for supporting him with a Post-doctoral fellowship. | |
| dc.identifier.doi | 10.1016/j.icheatmasstransfer.2020.104768 | |
| dc.identifier.eissn | 1879-0178 | |
| dc.identifier.issn | 0735-1933 | |
| dc.identifier.scopus | 2-s2.0-85088214638 | |
| dc.identifier.startpage | 104768 | |
| dc.identifier.uri | https://rdlopen.rawdatalibrary.net/r/ebyu/13331 | |
| dc.identifier.volume | 117 | |
| dc.identifier.wos | WOS:000576347700046 | |
| dc.language.iso | en | |
| dc.publisher | Elsevier Ltd | |
| dc.relation.ispartof | International Communications in Heat and Mass Transfer | |
| dc.rights | info:eu-repo/semantics/openAccess | |
| dc.subject | Boiling | |
| dc.subject | CHF | |
| dc.subject | Criticical heat flux | |
| dc.subject | Microchannel | |
| dc.subject | R134a | |
| dc.subject | Two phase flow | |
| dc.subject | Heat transfer coefficients | |
| dc.subject | Microchannels | |
| dc.subject | Absolute error | |
| dc.subject | Boiling heat transfer | |
| dc.subject | Critical heat flux(CHF) | |
| dc.subject | Experimental set up | |
| dc.subject | Hydraulic diameter | |
| dc.subject | Inlet temperature | |
| dc.subject | New correlations | |
| dc.subject | Saturation temperature | |
| dc.subject | Heat flux | |
| dc.title | Effect of saturation temperature and vapor quality on the boiling heat transfer and critical heat flux in a microchannel | |
| dc.type | Article | |
| dspace.entity.type | Publication | |
| rdl.citation.scopus | 19 | |
| rdl.citation.wos | 18 | |
| rdl.source.index | SCOPUS | |
| rdl.source.index | WOS | |
| rdl.wos.index | Science Citation Index Expanded (SCI-EXPANDED) |