Adaptive strategies and thermal perceptions in intermittently used congregational Spaces: A case study

ArticleAçık Erişim

Özet

In spaces with considerable volumes that are sporadically used and typically not operating at full capacity, existing thermal comfort models face limitations. This research aims to reveal disparities between these models and survey-based comfort assessments. Comfort calculations were conducted using conventional thermal comfort models based on measured parameters and compared with survey data. Notable differences prompted the formulation of a more robust correlation, accounting for 83.4 % of the variations in Predicted Mean Votes (PMV). A regression model derived from survey data shows a high coefficient of determination (R2 = 0.84), supporting its applicability for large intermittently used spaces like mosques. Addressing limitations of existing models, this research introduces a practical and simplified approach to predicting thermal comfort, enhancing assessments in these distinctive spaces. The study also examines mosque indoor air quality dynamics. Despite sporadic ventilation, CO2 levels rose from 1500 ppm to 2500 ppm during Friday prayers, posing potential health risks. Before prayers, indoor CO2 and humidity met ASHRAE Standard 62, ISO 7730, and EN15231 values. To mitigate health concerns from elevated CO2 levels, improved ventilation systems are necessary. Comfort temperatures were only achieved during prayer periods. © 2024

Anahtar Kelimeler

RDL Kalıcı Bağlantı (PID)
https://rdlopen.rawdatalibrary.net/r/ebyu/11208Resmi atıflarda kullanılan kalıcı adres
Tam Kayıt
AlanDeğerDil
dc.contributor.authorGemici, Zafer
dc.contributor.authorDogan, Ahmet
dc.date.accessioned2026-10-18T20:26:17.547036751Z
dc.date.available2026-10-18T20:26:17.547036751Z
dc.date.issued2024
dc.description.abstractIn spaces with considerable volumes that are sporadically used and typically not operating at full capacity, existing thermal comfort models face limitations. This research aims to reveal disparities between these models and survey-based comfort assessments. Comfort calculations were conducted using conventional thermal comfort models based on measured parameters and compared with survey data. Notable differences prompted the formulation of a more robust correlation, accounting for 83.4 % of the variations in Predicted Mean Votes (PMV). A regression model derived from survey data shows a high coefficient of determination (R2 = 0.84), supporting its applicability for large intermittently used spaces like mosques. Addressing limitations of existing models, this research introduces a practical and simplified approach to predicting thermal comfort, enhancing assessments in these distinctive spaces. The study also examines mosque indoor air quality dynamics. Despite sporadic ventilation, CO2 levels rose from 1500 ppm to 2500 ppm during Friday prayers, posing potential health risks. Before prayers, indoor CO2 and humidity met ASHRAE Standard 62, ISO 7730, and EN15231 values. To mitigate health concerns from elevated CO2 levels, improved ventilation systems are necessary. Comfort temperatures were only achieved during prayer periods. © 2024
dc.description.sponsorshipThis work was supported by the Yildiz Technical University Scientific Research Projects Coordination Unit under project number FBA-2020-3887.
dc.identifier.doi10.1016/j.jestch.2024.101828
dc.identifier.issn2215-0986
dc.identifier.scopus2-s2.0-85203990623
dc.identifier.startpage101828
dc.identifier.urihttps://rdlopen.rawdatalibrary.net/r/ebyu/11208
dc.identifier.volume58
dc.identifier.wosWOS:001317681600001
dc.language.isoen
dc.publisherElsevier B.V.
dc.relation.ispartofEngineering Science and Technology, an International Journal
dc.rightsinfo:eu-repo/semantics/openAccess
dc.subjectAdaptive response
dc.subjectIndoor air quality
dc.subjectIntermittently used space
dc.subjectSurvey study
dc.subjectThermal comfort
dc.titleAdaptive strategies and thermal perceptions in intermittently used congregational Spaces: A case study
dc.typeArticle
dspace.entity.typePublication
rdl.citation.scopus2
rdl.citation.wos1
rdl.oa.statusgold
rdl.source.indexSCOPUS
rdl.source.indexWOS
rdl.wos.indexScience Citation Index Expanded (SCI-EXPANDED)