Effect of Fire Damage on Seismic Behavior of Cast-in-Place Reinforced Concrete Columns

ArticleAçık Erişim

Özet

This paper presents the results of an experimental study that was conducted to investigate the postfire seismic behavior of reinforced concrete columns. Five full-scale, flexure-critical code-complying (e.g., ACI 318-14) cast-in-place reinforced concrete columns were tested to failure under a constant axial load and reversed cyclic lateral displacements after being exposed to an ISO-834 standard fire for 30, 60, and 90 min. Other than the effects of the duration of the fire exposure, the effects of the thickness of the concrete cover (25 and 40 mm) on the structural performance was also investigated for the short fire exposure duration (30 min). The responses of the columns were analyzed in terms of lateral load-displacement relationships, ductility, stiffness, energy dissipation capacities, and residual displacements. The test results indicated that the fire exposure reduced the lateral load capacity of the columns, whereas the deformability capabilities were found to be satisfactory in terms of a structural response. It was also observed that the thickness of the concrete cover had only a slight influence on the postfire seismic behavior of the columns. Furthermore, a numerical study was conducted to predict the load-displacement response of the fire exposed columns. The comparison of the experimentally and numerically obtained load-displacement relationships indicated that the principles of structural mechanics usually applied to conventional columns are also valid for the columns exposed to fire. (c) 2020 American Society of Civil Engineers.

Anahtar Kelimeler

RDL Kalıcı Bağlantı (PID)
https://rdlopen.rawdatalibrary.net/r/ebyu/16904Resmi atıflarda kullanılan kalıcı adres
Tam Kayıt
AlanDeğerDil
dc.contributor.authorDemir, Ugur
dc.contributor.authorGoksu, Caglar
dc.contributor.authorUnal, Goktug
dc.contributor.authorGreen, Mark
dc.contributor.authorIlki, Alper
dc.date.accessioned2026-10-18T20:41:07.787084113Z
dc.date.available2026-10-18T20:41:07.787084113Z
dc.date.issued2020
dc.description.abstractThis paper presents the results of an experimental study that was conducted to investigate the postfire seismic behavior of reinforced concrete columns. Five full-scale, flexure-critical code-complying (e.g., ACI 318-14) cast-in-place reinforced concrete columns were tested to failure under a constant axial load and reversed cyclic lateral displacements after being exposed to an ISO-834 standard fire for 30, 60, and 90 min. Other than the effects of the duration of the fire exposure, the effects of the thickness of the concrete cover (25 and 40 mm) on the structural performance was also investigated for the short fire exposure duration (30 min). The responses of the columns were analyzed in terms of lateral load-displacement relationships, ductility, stiffness, energy dissipation capacities, and residual displacements. The test results indicated that the fire exposure reduced the lateral load capacity of the columns, whereas the deformability capabilities were found to be satisfactory in terms of a structural response. It was also observed that the thickness of the concrete cover had only a slight influence on the postfire seismic behavior of the columns. Furthermore, a numerical study was conducted to predict the load-displacement response of the fire exposed columns. The comparison of the experimentally and numerically obtained load-displacement relationships indicated that the principles of structural mechanics usually applied to conventional columns are also valid for the columns exposed to fire. (c) 2020 American Society of Civil Engineers.
dc.description.sponsorshipThis research was supported by the Istanbul Technical University (ITU) Scientific Research Department (Project No. 39548) and the Scientific and Technological Research Council of Turkey under Grant No. 216M535. The authors are thankful to Yapi Merkezi Prefabrication Inc., Allianz Insurance Inc., Turk YTONG Inc., and Fibrobeton Inc. for financial support as well as the staff of ITU Structural and Earthquake Engineering, ITU Infrastructure Materials Laboratories, and the Fire Laboratory at the Turkish Standard Institute for their efforts.
dc.identifier.doi10.1061/sscest.1943-541x.0002794
dc.identifier.eissn1943-541X
dc.identifier.issn0733-9445
dc.identifier.issue11
dc.identifier.startpage4020232
dc.identifier.urihttps://rdlopen.rawdatalibrary.net/r/ebyu/16904
dc.identifier.volume146
dc.identifier.wosWOS:000576083900008
dc.language.isoen
dc.publisherASCE-AMER SOC CIVIL ENGINEERS
dc.relation.ispartofJOURNAL OF STRUCTURAL ENGINEERING
dc.rightsinfo:eu-repo/semantics/openAccess
dc.subjectColumns
dc.subjectEarthquake engineering
dc.subjectFire
dc.subjectReinforced concrete
dc.subjectSeismic
dc.subjectMECHANICAL-PROPERTIES
dc.subjectPERFORMANCE
dc.subjectRESISTANCE
dc.subjectEXPOSURE
dc.subjectConstruction & Building Technology
dc.subjectEngineering, Civil
dc.subjectEngineering
dc.titleEffect of Fire Damage on Seismic Behavior of Cast-in-Place Reinforced Concrete Columns
dc.typeArticle
dspace.entity.typePublication
rdl.citation.wos23
rdl.source.indexWOS
rdl.wos.indexScience Citation Index Expanded (SCI-EXPANDED)